  1.                          SECTION 16133
  2.  
  3.                    SURFACE METALLIC RACEWAYS
  4. NOTE ** This section is based on the 4000 Series surface
  5.         metallic raceway system manufactured by The
  6.         Wiremold Company, at the following address:
  7. NOTE **      60 Woodlawn Street
  8. NOTE **      West Hartford CT 06133-2500
  9. NOTE **      Tel. (800) 621-0049
  10. NOTE **      Fax. (203) 232-2062
  11. NOTE **
  12. NOTE ** The Wiremold Company offers a complete line of
  13.         products for communications, data, and electrical
  14.         wiring management.
  15. NOTE **
  16. NOTE ** SECTION 16133 - SURFACE METALLIC RACEWAYS,
  17.         Copyright 1998, The Architect's Catalog, Inc.
  18.  
  19.  
  20. PART 1  GENERAL
  21.  
  22. 1.1 SECTION INCLUDES
  23. NOTE ** Delete items below not required for project.
  24.     A.  Surface Metallic Raceways.
  25.  
  26.     B.  Fittings.
  27.  
  28.     C.  Device Brackets and Plates.
  29.  
  30.     D.  Cover Brackets and Face Plates.
  31.  
  32.     E.  Communications Devices and Accessories.
  33.  
  34.     F.  Electrical Devices.
  35.  
  36. 1.2 RELATED SECTIONS
  37. NOTE ** Add any sections below relevant to this project.
  38.  
  39.     A.  Sections of Division 16 affected by, or affecting,
  40.         construction activities of this section.
  41.  
  42. 1.3 REFERENCES
  43.  
  44.     A.  NFPA 70 - National Electrical Code.
  45.  
  46.     B.  UL 5 - Surface Metal Raceways and Fittings.
  47.  
  48.     C.  UL 94 - Test for Flammability of Plastic Materials for
  49.         Parts in Devices and Appliances.
  50.  
  51. 1.4 SYSTEM DESCRIPTION
  52.  
  53.     A.  Performance Requirements:
  54.         1.  Surface metallic raceway for dry interior locations,
  55.             conforming to National Electrical Code, Article 352,
  56.             Part B.
  57.         2.  System components listed by Underwriter's
  58.             Laboratories, Inc.:
  59.             a.  Metal components:  Conforming to specifications
  60.                 of UL 5.
  61.             b.  Plastic components:  Exhibiting non-flammable,
  62.                 self-extinguishing characteristics when tested in
  63.                 accordance with UL 94, V-O.
  64.  
  65. 1.5 SUBMITTALS
  66.  
  67.     A.  Submit under provisions of Section 01300.
  68.  
  69.     B.  Product Data:  Manufacturer's descriptive literature for
  70.         each system component specified in this section.
  71.  
  72.     C.  Shop Drawings:  Indicate raceway layouts, each system
  73.         component required for complete system, raceway lengths,
  74.         device types, locations; identify all circuits.
  75.  
  76.     D.  Quality Assurance Submittals:
  77.         1.  Test Reports:  Certified reports from independent
  78.             testing laboratory supporting compliance of raceway
  79.             system to specified requirements.
  80.         2.  Manufacturer's instructions:  Printed installation
  81.             instructions for each system component; include
  82.             storage requirements.
  83.  
  84.     E.  Closeout Submittals:  If variations from approved shop
  85.         drawings occur during installation of raceway system,
  86.         submit final as-built drawings indicating such
  87.         variations.
  88.  
  89. 1.6 DELIVERY, STORAGE, AND HANDLING
  90.  
  91.     A.  Store products of this section in manufacturer's unopened
  92.         packaging until installation.
  93.  
  94.     B.  Maintain storage area conditions for products of this
  95.         section in accordance with manufacturer's instructions
  96.         until installation.
  97.  
  98.  
  99. PART 2  PRODUCTS
  100.  
  101. 2.1 MANUFACTURERS
  102.  
  103.     A.  Acceptable Manufacturer:  The Wiremold Company;
  104.         60 Woodlawn Street, West Hartford CT 06133-2500; ASD.
  105.         Tel: (800) 621-0049, Fax: (203) 232-2062.
  106. NOTE ** Delete one of the two following paragraphs;
  107.         coordinate with Division 1 requirements.
  108.  
  109.     B.  Requests for substitutions will be considered in
  110.         accordance with provisions of Section 01600.
  111.  
  112.     C.  Substitutions:  Not permitted.
  113.  
  114. 2.2 COMPONENTS
  115.  
  116.     A.  Surface Metallic Raceways:
  117.         1.  Acceptable product:  Wiremold 4000 System.
  118.         2.  Product description:  Two-piece system of galvanized
  119.             steel, nominal 0.050 inch (1.27 mm) metal thickness,
  120.             having total assembled cross-section dimension 4.75
  121.             inches (120 mm) high by 1.75 inches (44 mm) deep,
  122.             having cross-section area 7.14 square inches (4606 sq
  123.             mm), consisting of the following:
  124.             a.  Base.
  125.             b.  Snap-on cover.
  126.             c.  Removable longitudinal barrier, dividing raceway
  127.                 interior into two equal spaces.
  128. NOTE ** Retain one of the following two sub-paragraphs to
  129.         specify finish.
  130.         3.  Finish:  Gray polyester topcoat over gray primer,
  131.             capable of being field-painted.
  132.         4.  Finish:  Ivory polyester topcoat over ivory primer,
  133.             capable of being field-painted.
  134.  
  135.     B.  Fittings:
  136.         1.  Factory-formed units to complete indicated
  137.             configuration of raceway systems, including, but not
  138.             limited to, the following:
  139.             a.  External corner units.
  140.             b.  Internal corner units.
  141.             c.  Flat units.
  142.             d.  Blank end units.
  143.             e.  Elbows.
  144.             f.  Couplings:  One per raceway joint location.
  145. NOTE ** Edit the following two sub-paragraphs if project
  146.         requirements differ.
  147.             g.  Wire clips:  One for every 2 linear feet (609 mm)
  148.                 of indicated raceway configuration.
  149.             h.  Replacement longitudinal barrier:  One section
  150.                 for every 5 linear feet (1524 mm) of indicated
  151.                 raceway configuration.
  152.         2.  Material:  Same material and metal thickness as
  153.             linear raceway components (0.40 inch [10 mm]
  154.             galvanized steel).
  155.         3.  Finish:  Matching linear raceway components.
  156.  
  157.     C.  Device Brackets and Plates:
  158.         1.  Factory-formed brackets and plates allowing
  159.             installation of indicated power, data, and
  160.             communications devices, both single-gang and two-
  161.             gang, either vertically or horizontally in raceways.
  162.         2.  Finish:  Color matching linear raceway components.
  163.  
  164.     D.  Cover Brackets and Face Plates:
  165.         1.  Plastic device mounting brackets and trim plates
  166.             allowing installation of indicated power, data, and
  167.             communications devices horizontally in raceways; trim
  168.             cover sized to overlap device cut-out in raceway,
  169.             concealing seams.
  170.         2.  Finish:  Color matching linear raceway components.
  171.  
  172.     E.  Communications Devices and Accessories:
  173.         1.  Communications devices:  Factory-fabricated
  174.             connectivity outlets, modular inserts, and other
  175.             devices for indicated configurations and service
  176.             requirements, including, but not limited to, the
  177.             following systems:
  178.             a.  UTP, including Category 5.
  179.             b.  STP; 150-ohm.
  180.             c.  Fiber Optics.
  181.             d.  Coaxial.
  182.         2.  Mounting face plates and bezels.
  183.         3.  Identification accessories, including the following:
  184.             a.  Pre-printed station and port identification
  185.                 labels.
  186.             b.  Snap-in icon buttons.
  187.             c.  Write-on station identification labels.
  188. NOTE ** Retain one of the following two paragraphs.
  189.  
  190.     F.  Electrical Devices:
  191.         1.  Factory-installed devices for indicated
  192.             configurations and service requirements.
  193.         2.  Finish of sight-exposed components:  Color matching
  194.             linear raceway components.
  195.  
  196.     G.  Electrical devices, and wiring for electrical devices,
  197.         are specified in sections of Division 16.
  198.  
  199.     H.  Fasteners:  Types specified in manufacturer's
  200.         installation instructions for project conditions.
  201.  
  202.  
  203. PART 3  EXECUTION
  204.  
  205. 3.1 EXAMINATION
  206.  
  207.     A.  Verification of Conditions:  Substrates are prepared to
  208.         receive products specified in this section.
  209.  
  210. 3.2 INSTALLATION
  211.  
  212.     A.  Install components of raceway system in accordance with
  213.         shop drawings and manufacturer's installation
  214.         instructions.
  215. NOTE ** Retain one or both of the following paragraphs, as
  216.         applicable to project.
  217.  
  218.     B.  Installation of electrical devices, and wiring of
  219.         electrical devices, is specified in a Division 16
  220.         section.
  221.  
  222.     C.  Installation of wiring for communications devices is
  223.         specified in a Division 16 section.
  224.  